Operating weights for the generator_transformer_set crane scenario (PRP-CALC-2). Four band tables: residential air-cooled gaseous generators, commercial diesel gensets (radiator model, wet), three-phase pad-mount transformers, and single-phase pad-mount transformers. weight_high_lb is the heaviest documented unit at/under the band ceiling; the derivation layer adds a stated rigging allowance and does not interpolate within a band. Diesel gensets between two cited kW anchors are sized by an explicitly-labeled linear heuristic (see derivation spec), mirroring the telehandler-interpolation precedent in crane_roofing.py. A rating outside all bands returns no match and the scenario asks for a known weight.

Access date for citations: 2026-07-12.

generator gaseous bands

band IDKW minKW maxweight high LBSource
gaseous_le_26kw026518GENERAC

generator diesel anchors

KWweight LBSource
1002,468KOHLER
1503,090KOHLER
1,00017,821KOHLER
1,30031,000KOHLER
2,00035,000KOHLER

transformer 3ph bands

band IDKVA minKVA maxweight high LB
3ph_le_75kva0752,100
3ph_le_150kva761502,600
3ph_le_300kva1513004,100
3ph_le_500kva3015005,100
3ph_le_750kva5017506,700
3ph_le_1000kva7511,0008,200
3ph_le_1500kva1,0011,50010,000
3ph_le_3000kva1,5013,00017,000
3ph_le_3750kva3,0013,75020,000

transformer 1ph bands

Transformer weights are from a single manufacturer's cut-sheet (Vantran). Pad-mount weight varies materially by voltage class, copper vs. aluminum windings, and cooling - flagged on output; verify against the actual nameplate before final sizing.

band IDKVA minKVA maxweight high LB
1ph_le_75kva0751,400
1ph_le_167kva761672,000
1ph_le_333kva1683333,100
1ph_le_500kva3345004,000